0:05 Hello everyone. Welcome back to Semi analysis weekly. I'm Jordan. Today I'm joined by Nico, Jeremy, and Harun, our first ever guest on the podcast. Up until this point, it's been all semi analysis people. Uh but now we're bringing on a guest because 800 volt DC adoption is too important. Uh we need to bring in the experts. Um yeah, Harun, welcome to the show. Do you mind starting by uh introducing yourself to the audience and and what you guys do?
0:29 Sure. Um, so Harun, co-founder and CEO of DG Matrix and I got into power electronics when it was extremely unpopular and a very uncool thing to do and and so now it's become much more popular. I've had a chance of of working on anything from computer room power which was a precursor to data centers. I've done solar inverters before the sun started shining on that industry. I've done transmission power flow control at hundreds of megawatt level using power electronics and even had a chance to pioneer some of the electronic jet engine starters all power electronics based on the Dreamliner and the joint strike fighter. So very and and now I think we're we're sitting on an extremely exciting era for humanity where the 800vt DC architecture is helping us propel propel the human race to to superhuman intelligence.
1:21 >> Awesome. Nico, why don't you uh kick things off with like one of, you know, a few questions. I I know you guys collaborated a little bit um to create the >> Yeah. >> part one of the 800 volt DC revolution article. >> So, yeah, sure. I mean, I think Hun already mentioned that the reason the main topic for this conversation is going to be 800 volts. I believe that it's been one of the main trends that we have been hearing all around during this 2026. We go to conferences and know there's a bolt pretty much everywhere.
1:53 All companies are know showcasing their side cars, their prototypes, pretty much everything. So you know the obvious question and before we get into the solid state transformers and all the cool stuff that we're going to cover today is Harun like why are we discussing 800 volt in 2026 today and why are we discussing 800 volts when we think about those 1 megawatt 1 megawatt racks. I think the the compute power required for GPUs in synchronicity is increasing to a point where legacy AC architecture and standard strands of AC cables are unable to carry the power.
2:35 And and and so the question is how high can you go in in in voltage that you can you can lower the the the cost and and remove the constraint of the copper delivery system. And so taking a 240 volts AC singlephase times three phases to to 800 volts effectively root mean square to root mean square you you you're going to get almost triple the power on on on the same copper cable provided you can handle the distribution. And I think those economics are are what's taking it to 800. So the second question would be well why not 1200? Why why why is it 800? Why is it not 950? and and I'm going to venture a a guess an educated guess that that one it has to do with EVs that that developed a lot of 800vt architecture but it also has to do with the fact that semiconductors the most popular semiconductor is the 1200vt device that that that is used in motor drives all over the world and so when silicon carbide and wide band gap came out they sort of came out for a 1200vt architecture and and with when the device can take that much then 800 volts is a good safe voltage to to settle on and maybe that's where some of the genesis of 800 volts is the power density the semiconductor ratings >> okay so I mean to put it simply for for the audience when you say enable to get the power required for these 600 kW 1 meg megawatt rocks is it a matter of you know we hear a lot about the weight of the bus bars because of the copper amount they will need to you know uh distribute all the current required uh to to to get into that power levels. Is it a weight matter? Is it a cost uh discussion because of you know we know about the price of the copper cost is just going up like crazy. Is it a matter of efficiency to lower down current and therefore I square I square our losses?
4:39 Is it a bit of everything in your opinion? what's the main you know driver for this whole revolution we we like to call it >> I think you you guys are very good at understanding the the physics and the economics right very impressive work that semi analysis does so so you've hit all the points and and I think it's it's uh it's how much current can you get and and generally when you raise the voltage you know as long as you have the separation the creepage and clearance raising voltage to get more power is far cheaper than raising current to get more power. And I think you're you're right.
5:15 So you're getting far more effective use out of the same um out of the same cuff. >> That's great. Um okay. I I I think you know the the foundation of why we were talking about that about this today it's it's now clear. Um of course like we are like being asked a lot on timings like oh is this something that's already happening? is something that this is going to you know start kicking off in two years. So just to put it simply in your opinion when does a handball become a necessity when a 100 bolt is more of a let's say still in the face of proof of concept? Um of course we have this news the the article with all these phases.
5:59 It's not I I I know it's not a short answer, but your opinion when does the 800 volt revolution really start to to kick off? >> I think it's it's uh started the the question is when does the right architecture from Nvidia come out that starts driving the demand and and when that comes out you can't say well I'm going to invent 800 volt architecture now you've got to do it upfront. So in a way that that that maturation of technology, the maturation of the manufacturing approach, the buildup of the supply chain and or or or migration of the supply chain from from the EV side to to the to the to the side of uh data centers has started already and and uh and but there's a big question and and it's interesting. We get this question a lot and and and and this is where we've come up with with a very unique solution using our multiport transformers. The question in customers minds is well how much percentage will DC be and how much percentage will AC be? If I go exclusively DC and the adoption rate is less than we want, are we going to be left with stranded power?
7:13 Are we going to be left with a stranded investment? And if we ignore AC and and those new companies that are coming out with chips that are going to run, let's say, less power or run on an AC architecture, then what do we do? Now, are we going to be in the same situation? And I think the answer we're gravitating towards is it shouldn't matter. You should have an architecture that's highly flexible that can do AC and DC in any percentage that you want right from the same uh same product line. And I think that's why people are so interested. So we just want to immunize the financial risk for the developers, the neoclouds and anybody else on on how much uh is DC, how much is AC and uh reduce the risk on the timing.
7:58 >> Yeah. Because I mean and I think your you know your last comment is a wonderful uh you know opportunity to introduce your your multipart products and how the value proposition of your multiport solutions. So just for the audience that's not maybe that familiar with DGatric and the multiple solutions, how do your solutions uh work and how do your tech take like different inputs, different voltages, different frequencies? So, one of the things that that I did back in 2011 to 2013 when I was working for an SST company is we were doing we were we were developing an SST, a solid state transformer to do AC conversion to AC conversion. And we were pitching like, oh, it'll clean up the power, it'll do this, it'll do that. But we realized after 2 years of work and and spending millions and millions of dollars that that was probably one of the dumbest things we could have done.
8:54 Why? It's because you're taking a a hunk of iron and a hunk of copper wound around it with some insulation that's going to last 40, 50 years, you know, and and it's going to last in heat and it's going to last in thermal cycles. Why the hell would anybody in their right mind try to replace that with a bunch of electronics that are going to be more delicate and and are going to cost a lot more and going to be less reliable? Why would anybody do that? And and so as we started to ask that question the answer was well it might be a great science experiment but that's where SSTs are going to stop. However the answer came that if you are look if you look at what happens to that AC after you transform it. Do you do variable AC with it? Do you do a motor drive at the end of it? Do you take a medium voltage and convert it to a low voltage? What do you do? And and so the answer is well if you combine for example the rectification function after the AC and and you put it all in an SST holy moly now you've got a balance of system that's actually cheaper it's more reliable because it's integrated it has less margin stacking because it's coming from one company and lo and behold you found the first value proposition for for the SST but it's AC to DC conversion so we started thinking further about it we're like well anybody can do that. You know what? What do how do you differentiate that? And so we came up with this crazy idea that if you're adding a port that does DC, you're adding much more value cuz you're collapsing a lot of the system that happens afterwards. So why not look at more ports? So we said, what if we added more AC ports? What if we added more DC ports? What if we could make every port birectional? and and and and so he said holy well the the word is something else but I'll I'll replace it with holy moly we said holy moly look at the value that you will add here and and you could replace a statcom you could replace a UPS a rectifier you could replace the energy management system you could replace behind the meter energy aggregation all with a multiport SST and we said boy that's the holy grail that's what we need to develop because the economics and the physics are all in your favor. And and so as we went down that path, we didn't realize that it it the controls, the the cooling, the electromagnetic interference, the density that we would have so many brick walls we would run into. So it took us, you know, at least 700,000 engineering hours to get multiport to a point where we could start doing deployments all over. And and that's how we came up with multiport is basically economics and physics driving innovation.
11:34 >> Okay. that that that's fascinating. That's that's truly fascinating. Um yeah, I I think you you know touch upon incredibly interesting points and I really don't want to be jumping you know from the very beginning of the competition we are having now until the that end state but you you mentioned like oh what if we take all these functions that can really UPS systems cover all these other part of the legacy electrical equipment. So just flash question before we go back into you know where we are today. But in your view when you think of the of the data center of of a data center in in five years in 10 years how does it look? How does the electrical architecture look? I I think clearly as densities increase, right?
12:20 The the number of um the the intelligence goes up, the the number of uh points that you uh compute goes up, the the the token the the cost of a token in kilowatt hours goes down. The question is what is going to drive that metric, right? Is is the cost of the token per kilowatt hour, assuming everything else is depreciated, it's going to come down to power, right? So when it comes down to power, it's power in, tokens out. So how do you get the absolute lowest cost of that token? And and and and how do you maximize that infrastructure is the answer? And and I think the voltages are probably going to go up at some point. People are already talking about 1500 volts DC. I think the density of the racks will probably go up and um and uh the racks are going to get smaller and smaller and smaller and the power infrastructure also has to follow a similar similar thing. That's where collapsing multiple systems into one makes sense. Not only do you get rid of a whole lot of copper and iron and junk, but you have far better functionality to eliminate stranded power and supply those dynamic loads. So that's where I I I think it's it's going to end up in far denser environments with even more integrated cooling. And >> that's that's fascinating. And yeah, it's like now that we have you here with us today, a great pleasure to have you here. It's just taking the opportunity to just go into your pick your brains and like know how you are envisioning these data centers looking 5 to 10 years out. But yeah, let's I would say let's go back to to to the present. Let's go back to today. Um today we are early early days of this whole revolution.
13:57 We're still even at a point that we hear about 800 balls as a whole. But you know when we look deeper into the systems look uh we we know about some hyperscalers working with plus - 400 volts some others are working directly looking it to into single-ended 800 volts just again put it simply for for the audience for everyone to to understand the implications of you know uh as an industry or from the perspective of dimetrics how you approach this what are the implications of going plus - 400 volts or going direct directly into 800 volts.
14:33 >> So, so the interesting thing is I think I think the the the question is what's driving plus - 400 volts versus 800 and is it a balanced plus - 400 volt load? That's that's the first question. And and I I tell you what, when we did the Dreamliner, um it's interesting whenever you fly something at those altitudes of 30 40,000 ft, the air is very different. the ionization of of of insulation happens in in a way where you degrade insulation above 300 volts. So the magic rule is you don't want to go above 300 volts and and so as density of of power goes up in airplanes. I mean it's gone up considerably from the 747 to the 787 and what's coming beyond it. It was like to to run 270 volt DC cables was untenable. So we came up with actually I think I think the guys who did the Dreamliner came up with this. let's run plus 270 and minus 270 with a common conductor in between and now you've got the best of both worlds and and so you're running 540 or or or whatever but not really from an ionization standpoint. And I'm wondering if the same thing drove the plus -400 vision but from a different physics the physics of arc flash. Was it that that arc flash is better understood at 4 500 volts DC and and there's a bigger perceived risk at 800? Um that that may have been where it came from and and so so so on the the competing architecture which is a close cousin is 800 volts without the third conductor. So if you have a balanced load the third conductor may be very very small but then you get into faults and then how do faults propagate? you get into the grounding schemes and it becomes a a nightmare for nonisolated converters and and and I think that's where uh it would be nice to get some harmonization. We frankly don't care which way it goes cuz we're a common we're every one of our ports is galvanically isolated and when it is you can float it anywhere you want. You can float it at minus 800. You can float it at 800. you can ground the center point and and get plus minus 400 and and we can use any grounding scheme that Nvidia is proposing in its um in its general reference architectures. Um, but I think it's it's going to come down to a conductor cost in which 800 might be cheaper and it might come down to u the the the opposite of that like how do you solve for arc flash and then again I think detection of arc flash and being able to quench the source from feeding the the the fault. I think that's where the magical answer will lie in setting the the a unified architecture hopefully >> the cost consideration that you mentioned is it just because in a bolt you have one conductor or less to to you know protect and to to control is just because of that or is there any other consideration when we think about the cost of different systems >> I I'm I'm sure there are many other considerations but I think that that copper cable the third copper cable for for for it is a significant consideration. Um um and and there may be many others. What I would do is is um we we can come back to you with a more comprehensive look of of what feeds that but but generally I think it's that copper it's that copper conductor.
17:51 >> Yeah. So on because we mentioned cost and complexity system complexity um when we think about you know Nvidia and Nvidia's partners working on initially this side car that's going to be single-ended 800 bolt what are the considerations when it comes to the complexity system is it actually more difficult to implement and designed a system that's using single-ended 800 volt compared to one that other um agents may may be working on that use plus - 400 volts.
18:26 >> I think the question the the essential question you have plus - 400 is are the loads going to be balanced at at 400 and - 400. If the load is not balanced, it's clearly a more complex system. And for example, you know, some fuel cells come at close to plus minus 400 and and so that's always going to be the question, can we just take power differentially? But if you can take power differentially, you have to treat it as two different circuits. So so that imbalance doesn't persist and it usually causes can cause in certain circuits a runaway condition where you collapse one voltage versus the other. So I I think uh there are reasons to favor a unipolar 800 volt as long as you can answer the arc flash um uh risk reduction uh properly. Um it also gives you a way to where you can do standardized grounding on the return conductor with a multiplicity of ways rather than worry about are you going to do grounding on on three conductors versus versus just the return one.
19:26 >> Makes sense. Um okay. So I'm I'm going to take this uh a little bit high higher level and talk about that like adoption curve let's say. So four phases right um whitespace retrofit native compute facility wide DC and then the end state of housing these SSTs. Uh maybe just to start the discussion here let me share uh a specific chart that you guys put in the 800vt DC article. Do you guys believe that this is, you know, a pretty solid uh adoption curve that's going to happen? Is there is there chances that this gets accelerated or gets pushed if that theoretical 1 megawatt rack like doesn't really come to fruition or or just the road map just gets pushed out?
20:09 Like for those who are uh just listening, we've got on on stage a on on on screen for the YouTube audience a chart that shows 800 volt DC adoption going from basically nothing in 2026 to almost 80% of the market by 2030 um in terms of like the incremental capacity that's being added to the data center market every year and um pushing above 30 gawatt worth of uh actual like adoption which is just unbelievable to think about but it it happens in phases where initially it's going to be a sidec car and then later it's going to be facility levelwide that it's actually happening. So what like what's your high level take when you see a chart like this? A high level take is it's always very difficult to project into the future and and and so while we we can't tell you whether these numbers are right or wrong we don't have any um special crystal ball we we do agree that there will be a market for sidecar that will go down over time as the native architecture for 800 volt DC takes root in AI data centers and and and so the question is yeah how long will that sidecar last especially when you have AC dominated architectures um and and you're doing a brownfield install it's far easier to do it with a sidecar or you're trying to mitigate the risk of u of not having the DC migration happen fast enough you go with an AC data center then you need the side car if it starts to happen and uh so yeah I think we generally agree with the shape but very difficult to predict the numbers we don't have that crystal ball and in our case we solved the problem both with a sidecar that we're developing as well and releasing through partners, but we're also developing that multiport that can handle the problem without a sidecar because you've got both DC and AC coming out. So, it's a different way of solving it for the whole data center. Yeah, >> Jordan, I think you you mentioned a really important point which is you know the possibility that this curve gets at least this place into the right uh for some time let's say a year or you know how many time and not not down just to the right >> it could be to the right it it could go up it could go longer it it it could go down faster it could be any one of those scenarios but the shift to the right may is very very possible you're right >> yeah it's possible in the sense that when thinking of this adoption curve, I mean we need to think it of this is what how we started the converation. This is a hardware and physicsdriven transition which is driven by these you know road maps of 600 kW uh racks. Uh suddenly and soon we will have one mega racks. If the systems that are extremely complex to designed and to adopt a large scale you know are delayed for a year uh or whatever like Nvidia roots maps for ultra get displays for a year we we we know that this happens and even especially when thinking of these super complex systems well this adoption curve will naturally just you know follow the hardware it's not you know it's this >> but it's not driven by the facilities so the concept of a sidecar is like I'm going to retrofit a facility that wasn't designed from the ground up to accept a multiC something that doesn't have a sidecar. You you don't it's not like sidecar design official to do. It's just really dependent on the site they're going into. Is that fair to say?
23:47 >> Yeah. Yeah. Um so an interesting parallel that we saw uh earlier this year u I guess last year as well was with chillers. Okay. Because Nvidia is pitching, hey, you can run your chillers at 45C when you're doing liquid cooling. And in theory, you can do it. But in practice, the share of folks running their chillers at that temperature is extremely low. And then the question is why, you know, it's more efficient. Supposedly, it's more energy efficient.
24:11 You can even save on capex if you do this. The problem is that the buyers themselves sort of don't really know exactly what their mix is going to be. And in fact, if you think about it, they've actually been proven right because you know, you would think maybe everything is GPUs and what we're realizing and you know, at seals been probably the first to call it out at the end of last year, CPUs are so back, right? So you're actually very much CPU constraint now as well. And so it actually makes sense if you have a limited data center footprint that you want your facilities to be able to handle many different types of hardware.
24:42 So the probably the biggest risk to SST adoption here would be the uncertainty on the hardware remains high. Um the timeline is part of it. The diversity of hardware is another one. In a world that is very largely say Nvidia and Nvidia's road map is 800 volts. Uh the decision is easier. But in a world where you have you know many different types of AS6 some of them maybe don't require 100 volts. Maybe CPUs are even more of a of a need which we actually are pretty bullish CPUs right now.
25:12 and storage and others. Uh it makes sense that you know you want your hardware to and your data centers um to be able to handle multiple types of hardware. And so you can it also goes goes back to like you know who is actually building the data centers and right now you have like this very interesting moment where the folks building the data centers for a big portion of them aren't actually the ones um the ones really using them. The big users are basically open AI and anthropic and you know the folks building dataers are Amazon and Microsoft who are building for openthropic and Amazon and Microsoft they both have this struggle which is that their business is very diversified.
25:49 They have a giant CPU cloud business as well. Um and so they they're they're like at the core of this uncertainty with regards to like what types of hardware am I going to deploy. um a few years down the road that could change. Um if folks like you know Open Penny, Anthropic start to self build, start to lease directly, they're going to have different requirements. They're going to be probably much more AI optimized in some of their designs and you know our institutional clients already know that pretty well. We've tal we've talked about this at length. Um but so these these sort of state of the industry right now where you have like different layers of third parties that are not the actual end users and so you have this uncertainty on what type of hard is being deployed. That's one of the risks to SST adoption and knowing it's going to be you know 28 29 2030 2031 for the very large scale numbers.
26:34 >> So I think I think by the way excellent points and and I agree with everything you said. The only thing I'd like to add in there is I think multiport SST even if I am biased solves that problem for you by allowing you to put any load on DC and any load on AC. So it derisks it for you. However, having said that, can I predict the adoption curve of multiport SST? No, I can't because because the hyperscalers are generally more conservative and and they have a right to be, right? They're building gazillion dollar data centers and they they are going to be a little bit more riskaverse, but the neoclouds and the data center developers may be more willing to take a risk to to make sure that their investment has a faster payback. So I think there's several ways to solve that problem. Uh we have one way that we think is very powerful. We we also have the sidecar way and we agree with you that it's going to be the CPUs, the GPUs, the TPUs, what power they use, how much goes to coloss, how much goes to AC loads, how much goes to DC loads, and and and and how much behind the meter power do you need? So there there's quite a bit of flux. That that is for sure. and and I think certain classes of SSTs are going to be at more risk of adoption versus other ones.
27:54 >> All right. And and I guess okay one one interesting question for you then is uh you said the multiport kind of solves the issue. Uh but the complication here is that obviously the electrical system of a data center is very complex. uh things have to be decided ahead of time and so I just wanted to like wait does multiport actually solve it because if you design your data ser if your whole distribution your switch gear and whatnot is you know AC then it's you're going to need a cycle regardless and if it's DC then you're going to do it DC based so multiports I guess that's better >> so a lot of folks that are looking at it with us are doing a hybrid that they want to do a certain amount on AC and a certain amount on DC and what we offer them in that case is you can put full load on DC or you can put full load on AC. As long as the two loads are under the full load rating of the machine, we don't care. We can give you both. So, it gives them the flexibility. We're also saying if you have DC today or AC today and you want to convert it to DC, we offer a very simple change out for for for our portion. You're not going to change the copper. You're going to change the protection and you offer a port switch out from AC to DC. That's what makes it easier uh to do it. So either buy both both and then you deal with the distribution especially with the protection um right the copper is not going to change. You're going to get much more out of your copper when you switch from AC to DC but you change the protection possibly the connectors and the whips and whatnot and and so it leaves you with an easier path when that transition happens.
29:28 >> And so actually that's I think a good transition to Nico's next banger article on industrials. uh because you know modular data center is like one topic we're looking at very closely and I guess you could imagine that if you if you're multiple then you can handle both easily then perhaps you know there's a world where you could use modular DCs and you know you have one module whatever 5 megawatt AC 5 meg DC 5 megs AC and then you know you can do whatever you want right like that could be an interesting I guess future for you guys and premier reference architectures u yeah >> yeah you know what I like about about uh the way you guys think right and it it's reflected in that 65page article uh and I think it's the most widely read publication from what I know a lot of our folks that called us up and said have you read this semi analysis piece were like wow you know these guys are really good but we like the way that you systematically think about it from the whole system perspective and not just focus on one little doohickey so my compliments to you in in looking at all the things uh on the load side and on the AI side that'll that'll cause architectural and technology adoption changes.
30:36 >> Always nice to hear self-promotion on the semi- analysis podcast. Haroon, thank you for that. Uh we will uh >> well in this case, you know, because a third party was doing it or your guest was doing it without the offer of a free cappuccino. I feel that it was genuine, right? So >> cappuccino coming your way next time, man. Um for sure. So um one thing that uh just coming from the Neocloud perspective, one thing that the hyperscalers always talk about is fungeability. They treat this at the fleet level, I think, where like different data centers might be used for different people or different things and then they they try to solve this with software. It seems like everything you're saying right now is making the case for fungibility at the power level um in the data center itself. Can you can you talk about like future proofing even beyond one megawatt? I mean for let let's actually sorry before I ask that question let's take a step back and go through the rack level power road map just for a second um because I uh I think maybe we we glossed over this a little bit or assumed that the general audience is is going to understand this. So let me let me put this on screen just so that we we know about this. when I started doing um you know design work on like uh compute systems for uh GPU servers it was in like 2016 2017 time frame and we were working on like the V100 the voltage generation systems and so like a rack which is a standard data center rack um that you might have in like US east one and aircooled CPUs for AWS is like 12 kilowatts and then 2020 start of COVID we started seeing more aircooled you know density go to 30 40 kilowatt per rack. We're now shipping today somewhere between 130 and 140 kilowatt per rack with the GB200 and GB300 systems. Um next year or potentially at the end of this year, uh Vera Rubin and and so what data centers were designed for two years ago or two to three years ago is 360 kilowatts per rack and then the Vera Rubin by the end of 2027 is 600 kilowatt per rack. So for the audience like that's already a massive we we have to put this chart on a log scale for those looking at it on screen because it's going up by 6x without the transition to 800 voltc even considered right when we say one one megawatt racks and what we're considering for the 2030 or or potentially 28 29 time frames is beyond a you know 60 times uh multiple of of power per rack. that that has had to be contended with. But now I'm going to ask the question which is uh what's the future proofing look like beyond this?
33:22 Let's say you build a data center um that's 100 megawatt scale uh which by the way I was in one of these facilities a week ago. It's absolutely unbelievable how much of the facility itself goes towards power and cooling as opposed to white space as opposed to like chips and data hall space now. Like well over 80% of the physical square footage is just power and cooling now. And so you know I can't even imagine what the future ones are going to look like. But let's say it's a 100 megawatt site or something like that. um gigawatt site even uh these sites are expected to to go for 15 years right and the whole case for fungibility on power I assume is like you're not going to rip out systems that you've deployed in the middle of their life it's just like we want to reuse this this facility for future systems in the future so is there stuff beyond um the current generation of systems if you push this out 10 15 years where you think SSTs would be able to be more capable of handling the future load at the end of a 15-ear life cycle for the data center facility itself that was built to handle those chips. Not only uh yeah I think I think so I think I think you have to look at a architecture that's going to deliver far more density it's going to be able to uh work with multiple sources behind the meter cuz that you know when you look at the transmission grid and the distribution grid even if you've got enough generation and and then you put a 100 megawatt data center at one spot you choke up all the lines around it that's why there's all this issue with well how am I going to improve my grid to get there. So the answer in the in the short run is well, I've got to do the behind the meter power until the grid upgrades.
35:06 But if the grid upgrades and the cost of grid goes up or or the cost of of depreciating that asset, that cost gets passed down in more expensive dollars per kilowatt hour, that means your token cost is going to go up. So So how do you leverage today's behind the meter power that you've put in and depreciated? Can you still continue to use it and leverage it and yet increase the density of delivery towards the racks that might go uh higher in power? And and and I think I think that maybe that may be one one thing to look at. The second thing to look at is it's sort of like this movie I saw a while ago where there's this gigantic 80 foot robot and and when it comes to a stock, the top opens up and a little kitty cat who's running the whole robot jumps out. That's how it is.
35:53 It's sort of like you got this massive power architecture and the brain which is the GPU stack keeps shrinking and shrinking and shrinking. So what geometry of the data center is going to uh optimize that that that brain shrinking? Is it going to be like a bicycle wheel where you've got power coming in from from multiple places and boom you pop down uh you know increasingly smaller set of GPUs that allow you to to handle that. And then and then what about superconducting? At what point uh does does superconducting kick in where you can where you can do five six megawws on on a strand of um cryogenically uh cooled uh cables that'll bring you unprecedented density and and then how do you distribute it to where any failure mode will not give you any stranded power and you can route the power to wherever the GPUs demand it for the cheapest token generation. or another way to look at it where you might even have an auctioning system for selling the the the the token generation to the highest bidder and and so I think there's going to be a tremendous amount of softwaredefined uh GPU scheduling a tremendous amount of softwaredefined power routing and and uh power handling at every single level.
37:14 There will be a cooling fabric. There will be a power fabric that can adapt to all these situations. And then there will be a a GPU job scheduling and and and whatnot as you look at different phases of of GPUs roll out. Now, it's also very conceivable, right? It's easy to brainstorm because because you you you're just thinking out the the reality making it real is different. But what about all these optical interfaces and all this optical computing that's coming out? Is that going to reverse the power density or will it keep power density and make it flat at some point where the optos kick in and reduce the amount of uh of uh of power that you need for the same amount of computation? Those are the questions and I I I'm smart enough to know that I'm not that smart and I don't have those answers on when it's going to happen or or how. But these are some things to think through.
38:04 >> I think we're um we're big believers in Jeban's paradox for everything including power. So even if you've got that optical stuff, I think we're going to still keep consuming quite a bit of power into the future. It's interesting to hear you say that specifically for behind the meter power generation. You think this is a trend that's going to continue? In other words, just building more facilities at the same site even if you get grid connected or just trying to deploy more chips in the same site. Um, do you think that's if if people are planning for 800 volt right now or planning big data centers you're working with them right now? Is this behind the meter trend more here to stay than we think?
38:45 >> I think Jordan that's an excellent question. I think I think so. I've done a lot of work on the distribution grid. I've done a lot of work on the transmission grid and and I've studied the economic models of of utilities, right? and and the world all all over the world utilities are generally they have they have unipolar or or unidirectional flow of power where power goes from generators down the transmission and distribution networks to where it's used and and upgrading that infrastructure is a multi multi-year time frame and and and so you've got you need hundreds of millions of dollars to do it. So, so I'm going I'm and and now you've got this this cellular power concept that we call where you can add 10 20 megawatt blocks at a time behind the meter and and start to add a gigawatt of distributed power.
39:35 So, which one is going to win out? And I think the speed to power or the speed to compute will win out. And for that reason, uh, distributed power generation and behind the meter power generation, which is another another word for it, is is is going to take root. And I don't think it's going to take root in just AI data centers. I think it's it's going to take root wherever you've got to develop uh electrical power delivery without the cost of a billion dollar nuclear plant or a10 billion nuclear plant. It's far easier to put a $5 million pod and give villagers a a hospital, give them a school, give them a chance to educate their kids. That's that's right. So, there's an electrification trend that's going to drive the the need to cellular power or behind the meter power, but there's the massive market right now at hand that's going to drive the volume to make uh make all the infrastructure for behind the meter power more palatable and drive the levelized cost of energy down. and then you adapt it to different areas. So, I think it's a disruption of a multi-t trillion dollar energy market.
40:41 Uh or or maybe not disruption, maybe that's too bold, maybe it's the augmentation of a centralized generation model of utilities with distributed generation augmenting it because it's far more far easier to deploy, far easy to redeploy and and and far more incremental investment with far faster payback. Yeah, that's that's really inspiring honestly to hear that framed that way where innovations that people are doing to serve the demand from coding assistant tokens right now is potentially I think highly likely to have a lot of positive downstream effects in all sorts of other industries that all just need a lot of power in the future.
41:21 >> That's right, Jordan. And and and think let's think about it, right? All of us on this call grew up with energy. I don't think we ever worried when we flipped a light switch on, right? We we had light to do our homework in. We had light for our we had power for our computers. We had access to the world's resources with the internet. We could charge our cell phones. But let's think about the world that didn't have power, right? Or or that part of the world that doesn't have power. They live a life of poverty. And the same thing is going to happen with AI. Those that can use AI and become really adept at it will create a further divide. So, so I think I think certainly for today for DG matrix shareholders, I got to focus on AI data centers, but there's a part of me that also is looking out at the electrification world and and that part that says you want to leave the world in a better place, you got to think of the rest of humanity and how you can help them in some way. So, yeah, I hope the AI data center not only drives us to superhuman intelligence, but makes power cheaper for everybody around the world.
42:20 Fusion or no fusion? Okay. >> You're offering up a lot of op options for where we can take those for the last few minutes of the podcast here. Nico Jeremy >> the double espresso. >> I guess you know just one thing I'm curious because you you mentioned um initially that that one of the reasons for 800 volts is because we reuse existing supply chains for example from automotive. Uh I'm just curious like for for you for your supply chain like do you actually use automotive suppliers and automotive vendors auto parts or is it just something completely yeah different?
42:53 >> No we use semiconductors that um the silicon carbide that was developed for 1200 volter architecture. Could some of those be used in in EVs? Yeah, some of those are used in EVs. And um do they give us a benefit? Yeah, I think they do. They they do. You have to look at um when when you are running these um surges, you've got to look at the physics of the semiconductor failure and and then you got to translate that to people who drive EVs who have a lead foot. There's a lot of commonality between all those surges and and so the people who have designed the physics to accommodate that there's some magic there.
43:29 >> Silicon carbide or gallium nitride for power electronics >> does doesn't matter. I I think it that right now silicon carbide is more apt to give you hundreds of kilowatts to to to megawws. Gallium nitrite is coming up. It's more suited for hundreds of watts to kilowatts. And and and quite frankly, as as I was discussing today in an investor panel, it shouldn't matter to those of us that want to deliver economic value to customers. The question is which one does a better job?
43:58 We're agnostic. We are actually we've been experimenting with both for 10 plus years and it's just silicon carbide is more mature at the right power levels right now >> or another one how how big can your SST get? Could we see a 10 megawatt unit a few years down the road? >> Yeah, actually the medium voltage SST that we're working on which is 35 KV in and and let's say 800 or 1500 volt programmable out that is designed for 10 megawatts in uh in one container. It's going to be one large container, but it's designed with higher voltage semiconductors. And uh on the on the front end and and and a divide down and and then and then a lower one and I think that's slated for 28, but 27 we're looking at the 6 megawatt SST. And today we have of course 400 kilowatt that we can parallel to multime.
44:48 >> Where are customers play expecting to play? Is it going to be in the gray space? Is it going to be outdoors? Is it going to >> certainly not going to be in the white space? And and you know what's interesting is in 2011 I worked on a product that was bringing medium voltage to the top of a rack. Um I can't talk much more about it but that was the first SST one of the first SSTs that we did. And and and really if you want to reduce the uh the cable to to copper or or get the most you got to bring medium voltage. But there's a lot of safety issues and architectural zoning issues and and whatnot and at at a national level. So it makes it tough. Maybe China would be the one to to get that done first. But uh but I think I think raising voltages and bringing bringing power and and and compute together in physical proximity is is one one trend that's taking root now.
45:40 >> Hey, speaking of uh China, is there any any kind of issues for you guys to source silicon carbide from China? >> We're not sourcing any silicon carbide from China. We're just sourcing it from the best folks we can we can find. and and and so our sources are are United States um potentially Japan but it's United States and Europe right now and and in yeah Europe Europe has two two very big suppliers for us and and then America right right there in North Carolina has a very big supplier for us too and that's what we're focusing on we are sourcing some you know nonCPU non-software electromechanical stuff from China but we have a China plus one sourcing uh strategy and so we can get the same parts from say Mexico or Vietnam and whatnot and we like everybody we're just trying to mitigate future risks.
46:28 >> All right. >> Okay. And I think one one thing I would just mention in in in going away is we think of all these architectures let's not forget that the more softwaredriven your power becomes the the better your cyber security must become because you don't want um third parties to hack into it. So we've developed and and deployed in the past cyber security proof power solutions on the transmission grid and and and that's a skill set that I think has to expand in the industry and if it doesn't you have the risk of uh of um you know misgreants coming in and taking your data center down. So, so let's make sure that um that's at some point we cover this too is how do you how do you really make uh uh make make this uh cyber security proof including background checks on every single entity that touches the electronics and develops the software.
47:20 >> Yeah, we don't want stuckset for any of these new big uh data centers. Seems pretty important. >> That's right. >> Yeah. Awesome. Okay. Well, guys, thank you so much. This was a whirlwind tour of 800 volt DC SSTs, all the implications on the supply chain. Appreciate you spending the time with us, Arun. Yeah, thanks to everybody who took the time to listen today. >> My compliments to semi analysis again. Thank you very much for the opportunity.
47:44 >> All right, take care, guys. Okay, bye-bye.
Summary
- 800-volt DC architecture is becoming crucial due to increasing power demands from GPUs and the limitations of legacy AC systems.
- The shift to higher voltages allows for more efficient power delivery, reducing the need for extensive copper wiring.
- The adoption curve for 800-volt systems is uncertain, influenced by hardware developments and the balance between AC and DC loads.
- Multiport solid-state transformers (SSTs) provide flexibility by accommodating both AC and DC loads, mitigating risks for developers.
- The future of data centers may involve higher power densities and integrated cooling solutions, with potential for superconducting technologies.
- Behind-the-meter power generation is expected to remain significant, allowing for more localized and efficient energy use.
- Cybersecurity considerations are essential as power systems become more software-driven, necessitating robust protections against potential threats.